HSL5510U Line Protection Measurement and Control Device
Application Scope
The HSL5510U line protection and monitoring device is suitable for line protection, measurement and control mainly based on current-type protection at voltage levels of 110kV and below. It can be installed locally on switchgears in a distributed manner or centrally in panels. It is equipped with communication interfaces and can form an automation system together with other protection and automation devices via the communication interfaces.
Function Configuration
|
Function |
Contents |
Function |
Contents |
|
Protection |
Three-stage definite-time directional phase overcurrent protection with undervoltage blocking |
Event Recording |
Protection events |
|
Inverse-time directional phase overcurrent protection (normal, very, extreme) |
Alarm events |
||
|
Three-stage definite-time directional zero-sequence overcurrent protection with zero-voltage blocking |
Remote signal change events |
||
|
Inverse-time directional zero-sequence overcurrent protection (normal, very, extreme) |
Operation record events |
||
|
Acceleration protection |
Event SOE |
||
|
Charging protection (post-acceleration protection) |
Fault change count statistics |
||
|
Overload protection |
Control |
Local/remote opening and closing |
|
|
Under-frequency load shedding |
Remote setting modification |
||
|
Under-voltage tripping |
Remote protection enable/disable |
||
|
Three-phase one-shot reclosing (non-synchronous, synchronous check, voltage-loss check) |
Operation Box |
Trip/close position indication |
|
|
Small current grounding |
Self-hold and anti-trip |
||
|
Grounding fault line selection and tripping |
Trip/close current self-adaptation |
||
|
Data Acquisition |
Current, voltage, active power, reactive power, power factor, frequency |
Control circuit break alarm |
|
|
10 remote signal channels |
Communi- cation |
Ethernet 1 (recommended) |
|
|
Fault recording |
Ethernet 2 (recommended) |
||
|
|
|
RS485 |
Nanjing Hosen Science and technology Co.,Ltd. was founded on October 20, 2003. It is located in the beautiful scenery of Jiangning Economic Development Zone in the ancient city of Nanjing. The company focuses on the research and development, production, operation and sales services of intelligent power grids, power system automation and relay protection products. It has been deeply engaged in the manufacturing of relay protection equipment, and with professional strength, has firmly established the foundation of the industry.
Address:No. 601, Building 10, Ji Yin Avenue 3118, Muling Sub-district, Jiangning District, Nanjing City, Jiangsu Province Telephone:025-84645390 Email:3100417487@qq.com